AGL Field CourseAirfield Ground Lighting for electricians, engineers and designers
ICAO Annex 14 · FAA AC 150/5340-30
IEC 61820 · 61821 · 61822 · 61823

The runway at night is an electrical system

Airfield Ground Lighting (AGL) is every light, sign and guidance aid on the movement area, plus the regulators, transformers and cable that keep each one at the right brightness. This course covers what pilots see, why the circuits are built the way they are, and how to size, maintain and fault-find them.

DANGER

Series circuits run at kilovolts. A constant current regulator will raise its output voltage to whatever it takes to push the set current, up to its rated maximum (about 4.5 kV for a 30 kVA, 6.6 A unit). Opening a primary circuit or an isolation transformer secondary while energised produces dangerous voltages.

Always isolate the regulator, open the series cutout, lock out, tag out and prove dead before work. This course is training material. It does not replace your aerodrome's procedures, the manufacturer's instructions or the current edition of the standards.

Why AGL uses series circuits

A runway edge circuit can be 5 to 10 km of cable with a hundred lights strung along it. On a parallel (constant voltage) feed, the lights at the far end would see a lower voltage and burn dimmer. Pilots judge distance and alignment from light patterns, so uneven brightness is not acceptable.

In a series circuit the same current flows through every light. A constant current regulator (CCR) holds that current at a set value, typically 6.6 A at full brightness. Every lamp sees the same current, so every lamp has the same intensity regardless of where it sits on the loop.

Each light connects to the loop through its own series isolation transformer. The primary winding is in series with the loop; the secondary feeds the lamp. When a lamp fails, the transformer keeps the loop closed and the rest stay lit.

The circuit, in four parts

CCRConverts the 400 V / 480 V supply into a regulated current (2.8 to 6.6 A) at whatever voltage the loop needs.
Primary cable5 kV class single-core cable running from the vault to every light base and back.
Isolation transformerOne per light. Keeps the loop closed when a lamp fails and isolates the lamp from the high-voltage primary.
FixtureHalogen lamp or LED engine, elevated on a frangible coupling or inset flush with the pavement.

Pick your track

Electrician / AGL technician

Keep it lit, safely

  1. Airfield lighting map: name every light by colour and position
  2. Series circuit simulator: what lamp failures and earth faults look like
  3. Maintenance & fault finding: LOTO, meggering, sectionalising
  4. Knowledge check, electrician questions
Electrical engineer

Understand the equipment

  1. Series circuit simulator: current, voltage, load
  2. CCRs, transformers, cable: types, protections, ratings
  3. Design calculators: CCR loading, insulation trends
  4. Fault finding: double earth faults, open circuits
System designer

Lay out compliant systems

  1. Airfield lighting map: CAT I vs CAT II/III patterns
  2. System design: circuits, interleaving, switch-over times
  3. CCR sizing calculator
  4. Knowledge check, designer questions

AGL Field Course is training material. Figures are typical values for learning purposes. Design, install and maintain airfield lighting to the current edition of the standards your aviation authority applies and to the equipment manufacturers' instructions.